3KW DC liquid cooling unit

Integrated design, saving on-site installation and commissioning costs;

Standard CAN communication interface;

High-voltage DC power supply, meeting the voltage range DC400V~800V;

Built-in pre-charging function to prevent instantaneous short circuit at high voltage power-up;

PTC heating meets the heating needs of equipment in low-temperature scenarios.

3KW DC liquid cooling unit
3KW DC liquid cooling unit
3KW DC liquid cooling unit
+
  • 3KW DC liquid cooling unit
  • 3KW DC liquid cooling unit
  • 3KW DC liquid cooling unit
project Units LCS0030W(DC version)
High voltage input power supply V DC650V(400~750V)
Low-voltage input power supply V DC24V(18~32V)
Cooling capacity KW 3(W18/L40°C)
Liquid supply flow L/min 15 
Supply pressure kPa 120
Cooling medium / 50% concentration of ethylene glycol solution
Refrigeration and liquid supply temperature 18
Refrigeration input power (high voltage side) KW 1.1 
Heat production KW 6(L-25°C)
Dimensions(W*D*H) mm 730*586*263
Installation: / Horizontal installation
Maximum SPL Noise (@1.5m@40°C) dB(A) ≤75(W18/L40℃,RH50%)
Waterproof and dustproof rating / Whole machine IP54 (electric control box IP56)
Refrigerants / R134a
life span Years >10
weight Medical history <40
Exterior color / RAL7035