Controllable temperature overcharging solution

Multi channel liquid supply, capable of cooling both liquid cooled DC modules and AC modules simultaneously;

Meet the liquid supply temperature requirement of 30 ℃ at an ambient temperature of 45 ℃;

The appearance design of the product is consistent with the overall style of the cabinet, and the entire cabinet is coordinated and beautiful;

Compatible with RS485 and TCP communication protocols, optional CAN communication;

Control the separate UPS power supply, and the liquid cooling unit will not go offline when the main power is cut off.

Controllable temperature overcharging solution
+
  • Controllable temperature overcharging solution
project unit GCS0250D
Mains power V/Hz 320~460V 50±2Hz
Auxiliary power supply V/Hz 220V±15%50±2Hz
Auxiliary power supply In <100
Cooling capacity @ ambient temperature 45°C   KW 25 
Feed temperature 30
Liquid supply flow L/min ≥100
Water resistance at the user end Kpa 100
Rated refrigeration input power   KW 8.2 
Energy efficiency ratio The above-mentioned 3.05
Maximum operating current A 18 
Methods of Communication / Ethernet
Dimensions(W*D*H) mm 1500X1206X600
Installation) / Top mounted
Noise (@1.0m away) dB(A) ≤70 (ambient temperature 45°C)
Waterproof and dustproof rating / IP55(Electric control panelIP56)
Refrigerants / R410A
Coolant / 50% ethylene glycol solution
life span Years >10
Exterior color / wrinkles
Corrosion protection level / C3